CPU processing times | |||
for bit operations, typ. | 150 ns; / instruction 1.2 µs; / instruction 3.6 µs; / instruction |
||
for word operations, typ. | |||
for floating point arithmetic, typ. | |||
Address area | |||
I/O address area | |||
● Inputs ● Outputs |
32 byte; Digital inputs 32 byte; Digital outputs |
||
Time of day | |||
Clock | |||
● Type ● Hardware clock (real-time) ● Backup time ● Deviation per day, max. |
Hardware clock, no battery backup Yes 7 d 4 s; within 120s/month at 25 °C |
||
Digital inputs | |||
Number of digital inputs | 36 | ||
Input voltage | |||
● Type of input voltage ● Rated value (DC) ● for signal “0” ● for signal “1” |
DC 24 V < 5 V DC +15 to +30 V |
||
Input current | |||
● for signal “1”, typ. | 4 mA | ||
Cable length | |||
● shielded, max. ● unshielded, max. |
500 m; 50m shielded for HSC inputs 300 m |
||
Digital outputs | |||
Number of digital outputs | 24; Relays | ||
Switching capacity of the outputs | |||
● with resistive load, max. ● on lamp load, max. |
2 A 30 W; 30 W with DC, 200 W with AC |
||
Relay outputs | |||
● Number of relay outputs | 24 | ||
Cable length | |||
● shielded, max. ● unshielded, max. |
500 m 150 m |
||
Interfaces | |||
Number of industrial Ethernet interfaces | 1 1 |
||
Number of RS 485 interfaces | |||
1. Interface | |||
Interface type | Ethernet Yes; Transformer isolated, 1,500V AC Yes; 10/100 Mbit/s Yes Yes |
||
Isolated | |||
automatic detection of transmission rate | |||
Autonegotiation | |||
Autocrossing | |||
Interface types | |||
● RJ 45 (Ethernet) | Yes | ||
2. Interface | |||
Interface type | RS 485 (max. 187.5 kbps) | ||
Protocols | |||
Supports protocol for PROFINET IO | Yes No |
||
PROFIBUS | |||
Protocols (Ethernet) | |||
● TCP/IP | Yes | ||
communication functions / header | |||
S7 communication | |||
● supported ● as server ● as client |
Yes
Yes Yes |
||
Test commissioning functions | |||
Forcing | |||
● Forcing | Yes | ||
Integrated Functions | |||
Counter ● Number of counters |
4; 4 at 100 kHz single phase or 2 at 50 kHz A/B phase Yes; PID closed-loop control function: Continuous controller outputs, binary controller outputs, automatic/manual mode, max. 8 loops |
||
PID controller | |||
EMC | |||
Interference immunity against discharge of static electricity | |||
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 | Yes | ||
— Test voltage at air discharge — Test voltage at contact discharge |
8 kV 4 kV |
||
Interference immunity against high-frequency electromagnetic fields | |||
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 | Yes; 10 V/m, 80 to 1 000 MHz (to IEC 61000-4-3); 10 V/m, 900 MHz, 1.89 GHz, 50% ED (to IEC 61000-4-3) |
||
Interference immunity to cable-borne interference | |||
● Interference immunity on supply lines acc. to IEC 61000- | Yes;
2 kV acc. to IEC 61000-4-4, burst |
||
4-4 | |||
● Interference immunity on signal cables acc. to IEC 61000- | Yes;
±2 kV acc. to IEC 61000-4-4, Burst |
||
4-4 | |||
Interference immunity against conducted variable disturbance induced by high-frequency fields | |||
● Interference immunity against high frequency current feed acc. to IEC 61000-4-6 | Yes;
10 V, 150 kHz to 80 MHz (to IEC 61000-4-6) |
||
Emission of radio interference acc. to EN 55 011 | |||
● Limit class A, for use in industrial areas | Yes;
EN 61000-6-4, interference emission: Intended for use in industrial areas. |
||
Emission of conducted and non-conducted interference | |||
● Interference emission via line/AC current cables | EN 61000-6-4, interference emission: Intended for use in industrial areas. | ||
Degree and class of protection | |||
IP degree of protection | IP20 | ||
Ambient conditions | |||
Free fall | |||
● Fall height, max. | 0.3 m; five times, in product package | ||
Ambient temperature during operation | |||
● min. | 0 °C | ||
● max. | 55 °C | ||
● horizontal installation, min. | 0 °C | ||
● horizontal installation, max. | 55 °C | ||
● vertical installation, min. | 0 °C | ||
● vertical installation, max. | 45 °C | ||
Ambient temperature during storage/transportation | |||
● min. | -40 °C | ||
● max. | 70 °C | ||
Air pressure acc. to IEC 60068-2-13 | |||
● Storage/transport, min. ● Storage/transport, max. |
660 hPa 1 080 hPa |
||
Altitude during operation relating to sea level | |||
● Installation altitude, min. ● Installation altitude, max. |
-1 000 m 2 000 m |
||
Relative humidity | |||
● Operation at 25 ℃ without condensation, max. | 95 % | ||
configuration / header | |||
configuration / programming / header | |||
Programming language | |||
— LAD — FBD — STL |
Yes YesYes |
||
Dimensions | |||
Width | 175 mm 81 mm 81 mm |
||
Height | |||
Depth | |||
Weights | |||
Weight, approx. | 620 g |