Interfaces | |
Interfaces/bus type | RS 422 / 485 (X.27) 1 |
Number of interfaces | |
Point-to-point connection | |
● Cable length, max. | 1 000 m |
Integrated protocol driver | |
— Freeport — ASCII — Modbus RTU master — MODBUS RTU slave — USS |
Yes Yes; Available as library function Yes Yes Yes; Available as library function |
Protocols | |
Integrated protocols | |
Freeport | |
— Telegram length, max. — Bits per character — Number of stop bits — Parity |
1 kbyte 7 or 8 1 (Standard), 2 No parity (standard); even, uneven, mark (parity bit always 1); space (parity bit always 0) |
3964 (R) | |
— Telegram length, max. — Bits per character — Number of stop bits — Parity |
1 kbyte 7 or 8 1 (Standard), 2 No parity (standard); even, uneven, mark (parity bit always 1); space (parity bit always 0) |
Modbus RTU master | |
— Address area — Number of slaves, max. |
1 through 49 999 (Standard Modbus addressing) 247; slave numbers 1 through 247, per MODBUS network segment maximum 32 devices, additional repeaters needed to expand the network to maximum configuration |
MODBUS RTU slave | |
— Address area | 1 through 49 999 (Standard Modbus addressing) |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Diagnostics indication LED | |
● for status of the outputs | Yes |
Degree and class of protection | |
IP degree of protection | IP20 |
Standards, approvals, certificates | |
CE mark | Yes
Yes Yes Yes Yes Yes Yes |
CSA approval | |
UL approval | |
cULus | |
FM approval | |
RCM (formerly C-TICK) | |
KC approval | |
Marine approval | |
Ambient conditions | |
Free fall | |
● Fall height, max. | 0.3 m; five times, in product package |
Ambient temperature during operation | |
● min. ● max. ● horizontal installation, min. ● horizontal installation, max. ● vertical installation, min. ● vertical installation, max. ● permissible temperature change |
-20 °C 60 °C -20 °C 60 °C -20 °C 50 °C 5°C to 55°C, 3°C / minute |
Ambient temperature during storage/transportation | |
● min. ● max. |
-40 °C 70 °C |
Air pressure acc. to IEC 60068-2-13 | |
● Operation, min. ● Operation, max. ● Storage/transport, min. ● Storage/transport, max. |
795 hPa 1 080 hPa 660 hPa 1 080 hPa |
Relative humidity | |
● Operation at 25 ℃ without condensation, max. | 95 % |
Dimensions | |
Width | 30 mm 100 mm 75 mm |
Height | |
Depth | |
Weights | |
Weight, approx. | 155 g |