Number of simultaneously controllable inputs | |
horizontal installation | |
— up to 40 °C, max. — up to 60 °C, max. |
32 16 |
vertical installation | |
— up to 40 °C, max. | 32 |
Input voltage | |
● Type of input voltage ● Rated value (DC) ● for signal “0” ● for signal “1” |
DC 24 V -30 to +5 V 13 to 30V |
Input current | |
● for signal “1”, typ. | 7 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
— parameterizable — at “0” to “1”, min. — at “0” to “1”, max. — at “1” to “0”, min. — at “1” to “0”, max. |
No 1.2 ms 4.8 ms 1.2 ms 4.8 ms |
Cable length | |
● shielded, max. ● unshielded, max. |
1 000 m 600 m |
Encoder | |
Connectable encoders | |
● 2-wire sensor — permissible quiescent current (2-wire sensor), max. |
Yes 1.5 mA |
Interrupts/diagnostics/status information | |
Alarms | No No |
Diagnostics function | |
Alarms | |
● Diagnostic alarm ● Hardware interrupt |
No No |
Diagnostics indication LED | |
● Status indicator digital input (green) | Yes |
Potential separation | |
Potential separation digital inputs | |
● between the channels ● between the channels, in groups of ● between the channels and backplane bus |
No 16 Yes; Optocoupler |
Isolation | |
Isolation tested with | 500 V DC |
connection method | |
required front connector | 40-pin |
Dimensions | |
Width | 40 mm 125 mm 120 mm |
Height | |
Depth | |
Weights | |
Weight, approx. | 260 g |