Address area | |||
I/O address area | |||
● Inputs ● Outputs |
144 byte; 256 bit of digital inputs & 56 words of analog inputs 144 byte; 256 bit of digital outputs & 56 words of analog outputs | ||
Time of day | |||
Clock | |||
● Type ● Hardware clock (real-time) ● Backup time |
Hardware clock, no battery backup Yes 7 d |
||
● Deviation per day, max. | 120 s; within 120s/month at 25 °C | ||
Digital inputs | |||
Number of digital inputs ● of which inputs usable for technological functions |
36; Integrated 6; HSC (High Speed Counting) Yes |
||
Source/sink input | |||
Number of simultaneously controllable inputs | |||
all mounting positions | |||
— up to 40 °C, max. | 36 | ||
Input voltage | |||
● Type of input voltage ● Rated value (DC) ● for signal “0” ● for signal “1” |
DC 24 V I0.0 to I0.3 < 1 V DC; I0.4 to I4.3 < 5 V DC I0.0 to I0.3 > 4V; I0.4 to I4.3 > 15V |
||
Input current | |||
● for signal “0”, max. (permissible quiescent current) ● for signal “1”, typ. |
1 mA 4 mA |
||
Input delay (for rated value of input voltage) | |||
for standard inputs | |||
— parameterizable — at “0” to “1”, min. — at “0” to “1”, max. |
Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four 0.2 ms 12.8 ms |
||
for interrupt inputs | |||
— parameterizable | Yes | ||
for technological functions | |||
— parameterizable | Yes; 6 Single phase: 4 HSCs at 200 kHz; 2 HSCs at 30 kHz 4 A/B phase: 2 HSCs at 100 kHz; 2 HSCs at 20 kHz |
||
Cable length | |||
● shielded, max. ● unshielded, max. |
500 m; 50m shielded for HSC inputs 300 m; for technological functions: No | ||
Digital outputs | |||
Number of digital outputs ● of which high-speed outputs |
24; Transistor 3; 100 kHz Pulse Train Output No |
||
Short-circuit protection | |||
Switching capacity of the outputs | |||
● with resistive load, max. ● on lamp load, max. |
0.5 A 5 W |
||
Output voltage | |||
● for signal “1”, min. | 20 V DC | ||
Output current | |||
● for signal “1” rated value ● for signal “0” residual current, max. |
0.5 A 10 µA |
||
Output delay with resistive load | |||
● “0” to “1”, max. ● “1” to “0”, max. |
3 µs; of the standard outputs, max. 3 µs; of the pulse outputs, max. (Q a.0 to Q a.3) 1 µs 200 µs; of the standard outputs, max. 200 µs; of the pulse outputs, max. (Q a.0 to Q a.3) 50 µs |
||
Switching frequency | |||
● of the pulse outputs, with resistive load, max. | 100 kHz | ||
Relay outputs | |||
● Number of relay outputs | 0 | ||
Cable length | |||
● shielded, max. ● unshielded, max. |
500 m 150 m |
||
Interfaces | |||
Number of industrial Ethernet interfaces | 1 1 |
||
Number of RS 485 interfaces | |||
1. Interface | |||
Interface type | PROFINET Yes; Transformer isolated, 1,500V AC Yes; 10/100 Mbit/s Yes |
||
Isolated | |||
automatic detection of transmission rate | |||
Autonegotiation | |||
Autocrossing | Yes | ||
Interface types | |||
● RJ 45 (Ethernet) | Yes | ||
Protocols | |||
● PROFINET IO Controller ● PROFINET IO Device |
Yes; Since V2.4 Yes; I-Device since V2.5 |
||
PROFINET IO Controller | |||
● Transmission rate, max. | 100 Mbit/s | ||
Services | |||
— Number of connectable IO Devices, max. — Updating time |
8 4 ms; The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. |
||
Address area | |||
— Inputs, max. — Outputs, max. |
128 byte; Per device 128 byte; Per device | ||
2. Interface | |||
Interface type | RS 485 (max. 187.5 kbps) | ||
Interface types | |||
● RS 485 | Yes | ||
PROFIBUS DP master | |||
Services | |||
— S7 communication | Yes | ||
Protocols | |||
Supports protocol for PROFINET IO | Yes; RT Controller (since FW V2.4) & I-Device (since FW V2.5) Yes; Via CM DP module |
||
PROFIBUS | |||
Protocols (Ethernet) | |||
● TCP/IP | Yes | ||
communication functions / header | |||
S7 communication | |||
● supported ● as server ● as client |
Yes Yes Yes |
||
Test commissioning functions | |||
Forcing | |||
● Forcing | Yes | ||
Integrated Functions | |||
Counter ● Number of counters |
6 Yes; PID closed-loop control function: Continuous controller outputs, binary controller outputs, automatic/manual mode, max. 8 loops 3 |
||
PID controller | |||
Number of pulse outputs | |||
EMC | |||
Interference immunity against discharge of static electricity | |||
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 — Test voltage at air discharge — Test voltage at contact discharge |
Yes 8 kV 4 kV |
||
Interference immunity against high-frequency electromagnetic fields | |||
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 | Yes; 10 V/m, 80 to 1 000 MHz (to IEC 61000-4-3); 10 V/m, 900 MHz, 1.89 GHz, 50% ED (to IEC 61000-4-3) |
||
Interference immunity to cable-borne interference | |||
● Interference immunity on supply lines acc. to IEC 61000- 4-4 ● Interference immunity on signal cables acc. to IEC 61000- 4-4 |
Yes; 2 kV acc. to IEC 61000-4-4, burst Yes; ±2 kV acc. to IEC 61000-4-4, Burst |
||
Interference immunity against conducted variable disturbance induced by high-frequency fields | |||
● Interference immunity against high frequency current feed acc. to IEC 61000-4-6 | Yes; 10 V, 150 kHz to 80 MHz (to IEC 61000-4-6) | ||
Emission of radio interference acc. to EN 55 011 | |||
● Limit class A, for use in industrial areas | Yes; EN 61000-6-4, interference emission: Intended for use in industrial areas. | ||
Emission of conducted and non-conducted interference | |||
● Interference emission via line/AC current cables | EN 61000-6-4, interference emission: Intended for use in industrial areas. | ||
Degree and class of protection | |||
IP degree of protection | IP20 | ||
Standards, approvals, certificates | |||
CE mark | Yes | ||
Ambient conditions | |||
Free fall | |||
● Fall height, max. | 0.3 m; five times, in product package | ||
Ambient temperature during operation | |||
● min. ● max. ● horizontal installation, min. ● horizontal installation, max. ● vertical installation, min. ● vertical installation, max. |
0 °C 55 °C 0 °C 55 °C 0 °C 45 °C |
||
Ambient temperature during storage/transportation | |||
● min. ● max. |
-40 °C 70 °C |
||
Air pressure acc. to IEC 60068-2-13 | |||
● Storage/transport, min. ● Storage/transport, max. |
660 hPa 1 080 hPa |
||
Altitude during operation relating to sea level | |||
● Installation altitude, min. ● Installation altitude, max. |
-1 000 m 2 000 m |
||
Relative humidity | |||
● Operation at 25 ℃ without condensation, max. | 95 % | ||
configuration / header | |||
configuration / programming / header | |||
Programming language | |||
— LAD — FBD — STL |
Yes Yes Yes |
||
Dimensions | |||
Width | 175 mm 100 mm 81 mm |
||
Height | |||
Depth | |||
Weights | |||
Weight, approx. | 528.2 g |