Detailed technical data Features
Module Configuration method |
I/O module Via software (Flexi Soft Designer) Safe EFI-pro System: Safety Designer |
|||||||||||||
Safety-related parameters | ||||||||||||||
Safety integrity level Category Performance level PFHD (mean probability of a dangerous fail- ure per hour) TM (mission time) |
SIL3 (IEC 61508) Category 4 (EN ISO 13849) PL e (EN ISO 13849) 4.8 x 10-9 (EN ISO 13849) 1) 0.9 x 10-9 (EN ISO 13849) 2) 20 years (EN ISO 13849) |
|||||||||||||
1) For single channel outputs. 2) For dual channel outputs. Functions |
||||||||||||||
Flexi Loop-compatible Fast shut-off Fast shut-off time |
✔ ✔ 8 ms |
|||||||||||||
Interfaces | ||||||||||||||
Number of safety inputs Number of test outputs Number of safe outputs Connection type |
8 2 4 Spring terminals |
|||||||||||||
Electrical data | ||||||||||||||
Protection class Voltage supply Internal power consumption |
III (EN 61140) Via FLEXBUS+ ≤ 2.2 W 1) |
|||||||||||||
Inputs Input voltage HIGH Input voltage LOW Input current HIGH Input current LOW Test outputs Voltage supply Type of output Test pulse generator Output voltage HIGH Output current |
13 V DC … 30 V DC –5 V DC … 5 V DC 2.4 mA    3.8 mA –2.5 mA    2.1 mA Via FLEXBUS+ PNP semiconductors, short-circuit protected 2 15 V DC    30 V DC ≤ 120 mA 2) |
|||||||||||||
Outputs Voltage supply Supply voltage Type of supply voltage Type of output Output voltage HIGH Output current |
Via A1, A2 24 V DC (16.8 V DC … 30 V DC) PELV or SELV 3) PNP semiconductors, short-circuit protected 16 V DC … 30 V DC ≤ 2 A |
|||||||||||||
1) Via FLEXBUS+, without streams at test outputs. 2) On each of the two test pulse generators. This makes max. 8 testable safe series connections possible per module, each with max. 30 mA. 3) The current of the power supply that powers the module must be limited to a maximum of 4 A, either through the power supply itself or a fuse. Mechanical data |
||||||||||||||
Dimensions (W x H x D) | 22.5 mm x 96.5 mm x 120.6 mm | |||||||||||||
Weight | 164 g (± 5 %) | |||||||||||||
Ambient data | ||||||||||||||
Enclosure rating | IP20 (EN 60529) | |||||||||||||
Ambient operating temperature | –25 °C … +55 °C | |||||||||||||
Storage temperature | –25 °C … +70 °C | |||||||||||||
Air humidity | ≤ 95 %, Non-condensing | |||||||||||||
Classifications | ||||||||||||||
eCl@ss 5.0 | 27243001 | |||||||||||||
eCl@ss 5.1.4 | 27243101 | |||||||||||||
eCl@ss 6.0 | 27243101 | |||||||||||||
eCl@ss 6.2 | 27243101 | |||||||||||||
eCl@ss 7.0 | 27243101 | |||||||||||||
eCl@ss 8.0 | 27243101 | |||||||||||||
eCl@ss 8.1 | 27243101 | |||||||||||||
eCl@ss 9.0 | 27243101 | |||||||||||||
eCl@ss 10.0 | 27243101 | |||||||||||||
eCl@ss 11.0 | 27243101 | |||||||||||||
eCl@ss 12.0 | 27243101 | |||||||||||||
ETIM 5.0 | EC001449 | |||||||||||||
ETIM 6.0 | EC001449 | |||||||||||||
ETIM 7.0 | EC001449 | |||||||||||||
ETIM 8.0 | EC001449 | |||||||||||||
UNSPSC 16.0901 | 32151705 |