Environmental | |||||||||||||
Ambient Air Temperature | Operation -25 … +55 °C Storage -40 … +70 °C |
||||||||||||
Reference Ambient Air Temperature |
30 °C | ||||||||||||
Degree of Protection | IP20 Enclosure with Cover IP40 |
||||||||||||
Pollution Degree | 2 | ||||||||||||
Environmental Conditions | 28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 % |
||||||||||||
Resistance to Vibrations acc. to IEC 60068-2-6 |
5g, 20 cycles at 5 … 150 … 5 Hz with load 0.8 In | ||||||||||||
Resistance to Shock acc. to IEC 60068-2-27 |
25g / 2 shocks / 13 ms | ||||||||||||
RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 | ||||||||||||
Environmental Information | 2CDK400030D0201 | ||||||||||||
REACH Declaration | 9AKK107492A1906 | ||||||||||||
Dimensions | |||||||||||||
Width in Number of Modular Spacings |
3 | ||||||||||||
Product Net Width | 52.5 mm | ||||||||||||
Product Net Height | 85 mm | ||||||||||||
Product Net Depth / Length |
69 mm | ||||||||||||
Product Net Weight | 0.375 kg | ||||||||||||
Pole Net Weight | 0.125 kg | ||||||||||||
Built-In Depth (t 2 ) | 69 mm | ||||||||||||
Container Information | |||||||||||||
Package Level 1 Units | carton 1 piece | ||||||||||||
Package Level 1 Width | 92 mm | ||||||||||||
Package Level 1 Height | 80 mm | ||||||||||||
Package Level 1 Depth / Length |
58 mm | ||||||||||||
Package Level 1 Gross Weight |
0.39 kg | ||||||||||||
Package Level 1 EAN |
|
||||||||||||
Package Level 2 Units | carton 36 piece | ||||||||||||
Package Level 2 Width | 275 mm | ||||||||||||
Package Level 2 Height | 210 mm | ||||||||||||
Package Level 2 Depth / Length |
395 mm | ||||||||||||
Package Level 2 Gross Weight |
14.8 kg | ||||||||||||
Package Level 2 EAN |
|
||||||||||||
Ordering | |||||||||||||
Minimum Order Quantity | 1 piece | ||||||||||||
Customs Tariff Number | 85362010 | ||||||||||||
Country of Origin | Germany (DE) | ||||||||||||
Certificates and Declarations (Document Number) | |||||||||||||
Certification Agency | EN IEC |
||||||||||||
Declaration of Conformity – CE |
2CDK400607D2703 | ||||||||||||
Environmental Information | 2CDK400030D0201 | ||||||||||||
Instructions and Manuals | 2CDS207105P0001 | ||||||||||||
REACH Declaration | 9AKK107492A1906 | ||||||||||||
RoHS Information | 2CDK400030D0201 | ||||||||||||
Popular Downloads | |||||||||||||
Data Sheet, Technical Information |
2CSC400030D0202 | ||||||||||||
Instructions and Manuals | 2CDS207105P0001 | ||||||||||||
Classifications | |||||||||||||
ETIM 7 | EC000042 – Miniature circuit breaker (MCB) | ||||||||||||
ETIM 8 | EC000042 – Miniature circuit breaker (MCB) | ||||||||||||
EPLAN Catalog Tree | Electrical engineering / Protection devices / General | ||||||||||||
EPLAN Function Definition |
Circuit breaker / Single circuit breaker / Circuit breaker 1_2 | ||||||||||||
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | ||||||||||||
WEEE B2C / B2B | Business To Business | ||||||||||||
CN8 | 8536 20 10 | ||||||||||||
UNSPSC | 39121603 | ||||||||||||
ABB-SH203-C3 Miniature Circuit Breaker – 3P – C – 3 A
Compact Home SH200 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection.
They are available in different characteristics (B,C), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 6 kA at 230/400 V
- AC) and rated currents (up to 40 A). All MCBs of the product range SH200 comply with IEC/EN 60898-1, allowing the use for residential
Dimensions | 275 × 210 × 395 cm |
---|---|
Standards |
IEC/EN 60898-1 |
Tripping Characteristic |
c |
Rated Operational |
acc. to IEC 60898-1 400 V AC |
Operational Voltage |
Maximum (Incl. Tolerance) 440 V AC Minimum 12 V AC |
Rated Insulation Voltage |
acc. to IEC/EN 60664-1 440 V |
Rated Impulse |
4 kV |
Withstand Voltage |
at 2000 m 5 kV |
Dielectric Test Voltage |
50/60 Hz, 1 min: 2 kV |
Input Voltage Type |
AC |
Rated Current (In) |
3 A |
Rated Short-Circuit |
(AC) 6 kA |
Rated Conditional Short |
(230 V) 6 kA |
Circuit Current (Inc) |
(400 V) 6 kA |
Rated Frequency (f) |
50 / 60 Hz |
Power Loss |
3.9W |
Power Supply |
Arbitrary |
Energy Limiting Class |
3 |
Mechanical Endurance |
20000 cycle |
Number of Poles |
3 |
Tightening Torque |
2 N·m |
Actuator Material |
Insulation Group II, Black, Sealable |
Accessories Available |
NO |
Connecting Capacity |
Conductor 25 / 25 mm² Flexible with Ferrule 0.75 … 16 mm² Flexible 0.75 … 16 mm² Rigid 0.75 … 25 mm² Stranded 0.75 … 25 mm² |
Terminal Type |
Screw Terminals |
Reviews