| CPU-blocks | |||||
| Number of blocks (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | ||||
| OB | |||||
| ● Number, max. | Limited only by RAM for code | ||||
| Data areas and their retentivity | |||||
| Retentive data area (incl. timers, counters, flags), max. | 14 kbyte | ||||
| Flag | |||||
| ● Size, max. | 8 kbyte; Size of bit memory address area | ||||
| Local data | |||||
| ● per priority class, max. | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | ||||
| Address area | |||||
| Process image | |||||
| ● Inputs, adjustable ● Outputs, adjustable |
1 kbyte 1 kbyte |
||||
| Hardware configuration | |||||
| Number of modules per system, max. | 3 comm. modules, 1 signal board, 8 signal modules | ||||
| Time of day | |||||
| Clock | |||||
| ● Hardware clock (real-time) ● Backup time ● Deviation per day, max. |
Yes 480 h; Typical ±60 s/month at 25 °C |
||||
| Digital inputs | |||||
| Number of digital inputs ● of which inputs usable for technological functions |
14; Integrated 6; HSC (High Speed Counting) Yes |
||||
| Source/sink input | |||||
| Number of simultaneously controllable inputs | |||||
| all mounting positions | |||||
| — up to 40 °C, max. | 14 | ||||
| Input voltage | |||||
| ● Rated value (DC) ● for signal “0” ● for signal “1” |
24 V 5 V DC at 1 mA 15 V DC at 2.5 mA |
||||
| Input delay (for rated value of input voltage) | |||||
| for standard inputs | |||||
| — parameterizable | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in | ||||
| groups of four | |||||
| — at “0” to “1”, min. | 0.2 ms | ||||
| — at “0” to “1”, max. | 12.8 ms | ||||
| for interrupt inputs | |||||
| — parameterizable | Yes | ||||
| for technological functions | |||||
| — parameterizable | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz | ||||
| Cable length | |||||
| ● shielded, max. ● unshielded, max. |
500 m; 50 m for technological functions 300 m; for technological functions: No | ||||
| Digital outputs | |||||
| Number of digital outputs | 10 | ||||
| ● of which high-speed outputs | 4; 100 kHz Pulse Train Output | ||||
| Limitation of inductive shutdown voltage to | L+ (-48 V) | ||||
| Switching capacity of the outputs | |||||
| ● with resistive load, max. | 0.5 A | ||||
| ● on lamp load, max. | 5 W | ||||
| Output voltage | |||||
| ● for signal “0”, max. ● for signal “1”, min. |
0.1 V; with 10 kOhm load 20 V |
||||
| Output current | |||||
| ● for signal “1” rated value ● for signal “0” residual current, max. |
0.5 A 0.1 mA |
||||
| Output delay with resistive load | |||||
| ● “0” to “1”, max. ● “1” to “0”, max. |
1 µs 5 µs |
||||
| Switching frequency | |||||
| ● of the pulse outputs, with resistive load, max. | 100 kHz | ||||
| Relay outputs | |||||
| ● Number of relay outputs | 0 | ||||
| Cable length | |||||
| ● shielded, max. ● unshielded, max. |
500 m 150 m |
||||
| Analog inputs | |||||
| Number of analog inputs | 2 | ||||
| Input ranges | |||||
| ● Voltage | Yes | ||||
| Input ranges (rated values), voltages | |||||
| ● 0 to +10 V — Input resistance (0 to 10 V) |
Yes ≥100k ohms |
||||
| Cable length | |||||
| ● shielded, max. | 100 m; twisted and shielded | ||||
| Analog outputs | |||||
| Number of analog outputs | 0 | ||||
| Analog value generation for the inputs | |||||
| Integration and conversion time/resolution per channel | |||||
| ● Resolution with overrange (bit including sign), max. ● Integration time, parameterizable ● Conversion time (per channel) |
10 bit Yes 625 µs | ||||
| Encoder | |||||
| Connectable encoders | |||||
| ● 2-wire sensor | Yes | ||||
| 1. Interface | |||||
| Interface type | PROFINET Yes Yes Yes Yes |
||||
| Isolated | |||||
| automatic detection of transmission rate | |||||
| Autonegotiation | |||||
| Autocrossing | |||||
| Interface types | |||||
| ● RJ 45 (Ethernet) ● Number of ports ● integrated switch |
Yes 1 No |
||||
| Protocols | |||||
| ● PROFINET IO Controller ● PROFINET IO Device ● SIMATIC communication ● Open IE communication ● Web server ● Media redundancy |
Yes
Yes Yes |
||||
| PROFINET IO Controller | |||||
| ● Transmission rate, max. | 100 Mbit/s | ||||
| Services | |||||
| — PG/OP communication — Isochronous mode — IRT — PROFIenergy — Prioritized startup — Number of IO devices with prioritized startup, max. — Number of connectable IO Devices, max. — Number of connectable IO Devices for RT, max. — of which in line, max. |
Yes; encryption with TLS V1.3 pre-selected No No No Yes 16 16 16 16 |
||||
| — Activation/deactivation of IO Devices — Number of IO Devices that can be simultaneously activated/deactivated, max. — Updating time |
Yes 8 The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. |
||||
| PROFINET IO Device | |||||
| Services | |||||
| — PG/OP communication — Isochronous mode — IRT — PROFIenergy — Shared device — Number of IO Controllers with shared device, max. |
Yes; encryption with TLS V1.3 pre-selected No No Yes Yes 2 |
||||
| Protocols | |||||
| Supports protocol for PROFINET IO | Yes No Yes; CM 1243-5 (master) or CM 1242-5 (slave) required Yes; OPC UA Server Yes; CM 1243-2 required |
||||
| PROFIsafe | |||||
| PROFIBUS | |||||
| OPC UA | |||||
| AS-Interface | |||||
| Protocols (Ethernet) | |||||
| ● TCP/IP ● DHCP ● SNMP ● DCP ● LLDP |
Yes No Yes Yes Yes | ||||
| Redundancy mode | |||||
| Media redundancy | |||||
| — MRP — MRPD |
No No |
||||
| SIMATIC communication | |||||
| ● S7 routing | Yes | ||||
| Open IE communication | |||||
| ● TCP/IP — Data length, max. ● ISO-on-TCP (RFC1006) — Data length, max. ● UDP — Data length, max. |
Yes 8 kbyte Yes 8 kbyte Yes 1 472 byte |
||||
| Web server | |||||
| ● supported ● User-defined websites |
Yes
Yes |
||||
| OPC UA | |||||
| ● Runtime license required ● OPC UA Server — Application authentication — User authentication — Number of sessions, max. — Number of subscriptions per session, max. — Sampling interval, min. — Publishing interval, min. — Number of server methods, max. — Number of monitored items, recommended max. — Number of server interfaces, max. — Number of nodes for user-defined server interfaces, max. |
Yes; “Basic” license required Yes; data access (read, write, subscribe), method call, runtime license required Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 “anonymous” or by user name & password 10 5 100 ms 200 ms 20 1 000 2 2 000 |
||||
| Further protocols | |||||
| ● MODBUS | Yes | ||||
| communication functions / header | |||||
| S7 communication | |||||
| ● supported | Yes | ||||
| ● as server ● as client ● User data per job, max. |
Yes Yes See online help (S7 communication, user data size) |
||||
| Number of connections | |||||
| ● overall | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max |
||||
| Test commissioning functions | |||||
| Status/control | |||||
| ● Status/control variable ● Variables |
Yes Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
||||
| Forcing | |||||
| ● Forcing | Yes | ||||
| Diagnostic buffer | |||||
| ● present | Yes | ||||
| Traces | |||||
| ● Number of configurable Traces ● Memory size per trace, max. |
2 512 kbyte |
||||
| Interrupts/diagnostics/status information | |||||
| Diagnostics indication LED | |||||
| ● RUN/STOP LED ● ERROR LED ● MAINT LED |
Yes
Yes |
||||
| Integrated Functions | |||||
| Counter ● Number of counters ● Counting frequency, max. |
6 100 kHz Yes Yes 8 4; With integrated outputs Yes 4 4 100 kHz |
||||
| Frequency measurement | |||||
| controlled positioning | |||||
| Number of position-controlled positioning axes, max. | |||||
| Number of positioning axes via pulse-direction interface | |||||
| PID controller | |||||
| Number of alarm inputs | |||||
| Number of pulse outputs | |||||
| Limit frequency (pulse) | |||||
| Potential separation | |||||
| Potential separation digital inputs | |||||
| ● Potential separation digital inputs ● between the channels, in groups of |
No 1 |
||||
| Potential separation digital outputs | |||||
| ● Potential separation digital outputs ● between the channels ● between the channels, in groups of |
Yes No 1 |
||||
| EMC | |||||
| Interference immunity against discharge of static electricity | |||||
| ● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 — Test voltage at air discharge — Test voltage at contact discharge |
Yes 8 kV 6 kV |
||||
| Interference immunity to cable-borne interference | |||||
| ● Interference immunity on supply lines acc. to IEC 61000- 4-4 ● Interference immunity on signal cables acc. to IEC 61000- 4-4 |
Yes Yes |
||||
| Interference immunity against voltage surge | |||||
| ● Interference immunity on supply lines acc. to IEC 61000- 4-5 | Yes | ||||
| Interference immunity against conducted variable disturbance induced by high-frequency fields | |||||
| ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 | Yes | ||||
| Emission of radio interference acc. to EN 55 011 | |||||
| ● Limit class A, for use in industrial areas | Yes; Group 1 | ||||
| ● Limit class B, for use in residential areas | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | ||||
| Degree and class of protection | |||||
| IP degree of protection | IP20 | ||||
| Standards, approvals, certificates | |||||
| CE mark | Yes
Yes Yes Yes Yes Yes |
||||
| UL approval | |||||
| cULus | |||||
| FM approval | |||||
| RCM (formerly C-TICK) | |||||
| KC approval | |||||
| Marine approval | |||||
| Ambient conditions | |||||
| Free fall | |||||
| ● Fall height, max. | 0.3 m; five times, in product package | ||||
| Ambient temperature during operation | |||||
| ● min. ● max. ● horizontal installation, min. ● horizontal installation, max. ● vertical installation, min. ● vertical installation, max. |
-20 °C 60 °C; Number of simultaneously activated inputs or outputs 7 or 5 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 14 or 10 at 55 °C horizontal or 45 °C vertical -20 °C 60 °C -20 °C 50 °C |
||||
| Ambient temperature during storage/transportation | |||||
| ● min. ● max. |
-40 °C 70 °C |
||||
| Air pressure acc. to IEC 60068-2-13 | |||||
| ● Operation, min. ● Operation, max. ● Storage/transport, min. ● Storage/transport, max. |
795 hPa 1 080 hPa 660 hPa 1 080 hPa |
||||
| Altitude during operation relating to sea level | |||||
| ● Installation altitude, min. ● Installation altitude, max. |
-1 000 m 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
||||
| Relative humidity | |||||
| ● Operation, max. | 95 %; no condensation | ||||
| Vibrations | |||||
| ● Vibration resistance during operation acc. to IEC 60068- 2-6 ● Operation, tested according to IEC 60068-2-6 |
2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail Yes |
||||
| Shock testing | |||||
| ● tested according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | ||||
| Pollutant concentrations | |||||
| ● SO2 at RH < 60% without condensation | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | ||||
| configuration / header | |||||
| configuration / programming / header | |||||
| Programming language | |||||
| — LAD — FBD — SCL |
Yes
Yes Yes |
||||
| Know-how protection | |||||
| ● User program protection/password protection ● Copy protection ● Block protection |
Yes YesYes |
||||
| Access protection | |||||
| ● protection of confidential configuration data ● Protection level: Write protection ● Protection level: Read/write protection ● Protection level: Complete protection |
Yes
Yes Yes Yes |
||||
| programming / cycle time monitoring / header | |||||
| ● adjustable | Yes | ||||
| Dimensions | |||||
| Width | 110 mm 100 mm 75 mm |
||||
| Height | |||||
| Depth | |||||
| Weights | |||||
| Weight, approx. | 415 g | ||||

Reviews