CPU-blocks | ||||||
Number of blocks (total) | 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. | |||||
DB | ||||||
● Number, max. ● Size, max. |
1 024; Number range: 1 to 16000 64 kbyte |
|||||
FB | ||||||
● Number, max. ● Size, max. |
1 024; Number range: 0 to 7999 64 kbyte |
|||||
FC | ||||||
● Number, max. ● Size, max. |
1 024; Number range: 0 to 7999 64 kbyte |
|||||
OB | ||||||
● Number, max. ● Size, max. ● Number of free cycle OBs ● Number of time alarm OBs ● Number of delay alarm OBs ● Number of cyclic interrupt OBs ● Number of process alarm OBs ● Number of DPV1 alarm OBs ● Number of startup OBs ● Number of asynchronous error OBs ● Number of synchronous error OBs |
see instruction list 64 kbyte 1; OB 1 1; OB 10 2; OB 20, 21 4; OB 32, 33, 34, 35 1; OB 40 3; OB 55, 56, 57 1; OB 100 5; OB 80, 82, 85, 86, 87 2; OB 121, 122 |
|||||
Nesting depth | ||||||
● per priority class ● additional within an error OB |
16 4 |
|||||
Counters, timers and their retentivity | ||||||
S7 counter | ||||||
● Number | 256 | |||||
Retentivity | ||||||
— adjustable — lower limit — upper limit — preset |
Yes 0 255 Z 0 to Z 7 |
|||||
Counting range | ||||||
— lower limit — upper limit |
0 999 |
|||||
IEC counter | ||||||
● present ● Type ● Number |
Yes SFB Unlimited (limited only by RAM capacity) |
|||||
S7 times | ||||||
● Number | 256 | |||||
Retentivity | ||||||
— adjustable — lower limit — upper limit — preset |
Yes 0 255 No retentivity |
|||||
Time range | ||||||
— lower limit — upper limit |
10 ms 9 990 s |
|||||
IEC timer | ||||||
● present ● Type ● Number |
Yes SFB Unlimited (limited only by RAM capacity) |
|||||
Data areas and their retentivity | ||||||
Retentive data area (incl. timers, counters, flags), max. | 64 kbyte | |||||
Flag | ||||||
● Size, max. ● Retentivity available ● Retentivity preset ● Number of clock memories |
256 byte Yes; MB 0 to MB 255 MB 0 to MB 15 8; 1 memory byte |
|||||
Data blocks | ||||||
● Retentivity adjustable ● Retentivity preset |
Yes; via non-retain property on DB Yes |
|||||
Local data | ||||||
● per priority class, max. | 32 kbyte; Max. 2048 bytes per block | |||||
Address area | ||||||
I/O address area | ||||||
● Inputs ● Outputs |
2 048 byte 2 048 byte |
|||||
of which distributed | ||||||
— Inputs — Outputs |
2 003 byte 2 010 byte |
|||||
Process image | ||||||
● Inputs ● Outputs ● Inputs, adjustable ● Outputs, adjustable ● Inputs, default ● Outputs, default |
2 048 byte 2 048 byte 2 048 byte 2 048 byte 128 byte 128 byte |
|||||
Default addresses of the integrated channels | ||||||
— Digital inputs — Digital outputs — Analog inputs — Analog outputs |
124.0 to 126.7 124.0 to 125.7 752 to 761 752 to 755 |
|||||
Digital channels | ||||||
● Inputs — of which central ● Outputs — of which central |
16 048 1 016 16 096 1 008 |
|||||
Analog channels | ||||||
● Inputs — of which central ● Outputs — of which central |
1 006 253 1 007 250 |
|||||
Hardware configuration | ||||||
Number of expansion units, max. | 3 | |||||
Number of DP masters | ||||||
● integrated ● via CP |
1 4 |
|||||
Number of operable FMs and CPs (recommended) | ||||||
● FM ● CP, PtP ● CP, LAN |
8 8 10 |
|||||
Rack | ||||||
● Racks, max. ● Modules per rack, max. |
4 8; In rack 3 max. 7 |
|||||
Time of day | ||||||
Clock | ||||||
● Hardware clock (real-time) ● retentive and synchronizable |
Yes Yes | |||||
● Backup time ● Deviation per day, max. ● Behavior of the clock following POWER-ON ● Behavior of the clock following expiry of backup period |
6 wk; At 40 °C ambient temperature 10 s; Typ.: 2 s Clock continues running after POWER OFF the clock continues at the time of day it had when power was switched off |
|||||
Operating hours counter | ||||||
● Number ● Number/Number range ● Range of values ● Granularity ● retentive |
1 0 0 to 2^31 hours (when using SFC 101) 1 h Yes; Must be restarted at each restart |
|||||
Clock synchronization | ||||||
● supported ● to MPI, master ● to MPI, slave ● to DP, master ● to DP, slave ● in AS, master ● in AS, slave |
Yes
Yes Yes |
|||||
Digital inputs | ||||||
Number of digital inputs ● of which inputs usable for technological functions |
24 16 24 Yes |
|||||
integrated channels (DI) | ||||||
Input characteristic curve in accordance with IEC 61131, type 1 | ||||||
Number of simultaneously controllable inputs | ||||||
horizontal installation | ||||||
— up to 40 °C, max. — up to 60 °C, max. |
24 12 |
|||||
vertical installation | ||||||
— up to 40 °C, max. | 12 | |||||
Input voltage | ||||||
● Rated value (DC) ● for signal “0” ● for signal “1” |
24 V -3 to +5V +15 to +30 V |
|||||
Input current | ||||||
● for signal “1”, typ. | 8 mA | |||||
Input delay (for rated value of input voltage) | ||||||
for standard inputs | ||||||
— parameterizable — Rated value |
Yes; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of the standard inputs during program runtime. Please note that under certain circumstances your newly set filter time may not be effective until the next filter cycle.) 3 ms |
|||||
for technological functions | ||||||
— at “0” to “1”, max. | 8 µs; Minimum pulse width/minimum pause between pulses at maximum counting frequency | |||||
Cable length | ||||||
● shielded, max. ● unshielded, max. |
1 000 m; 50 m for technological functions 600 m; for technological functions: No | |||||
for technological functions | ||||||
— shielded, max. — unshielded, max. |
50 m; at maximum count frequency not allowed | |||||
Digital outputs | ||||||
Number of digital outputs ● of which high-speed outputs |
16 4; Notice: You cannot connect the fast outputs of your CPU in parallel 16 Yes; Clocked electronically 1 A L+ (-48 V) Yes |
|||||
integrated channels (DO) | ||||||
Short-circuit protection ● Response threshold, typ. |
||||||
Limitation of inductive shutdown voltage to | ||||||
Controlling a digital input | ||||||
Switching capacity of the outputs | ||||||
● on lamp load, max. | 5 W | |||||
Load resistance range | ||||||
● lower limit ● upper limit |
48 Ω 4 kΩ |
|||||
Output voltage | ||||||
● for signal “1”, min. | L+ (-0.8 V) | |||||
Output current | ||||||
● for signal “1” rated value ● for signal “1” permissible range, min. ● for signal “1” permissible range, max. ● for signal “1” minimum load current ● for signal “0” residual current, max. |
500 mA 5 mA 0.6 A 5 mA 0.5 mA |
|||||
Parallel switching of two outputs | ||||||
● for uprating ● for redundant control of a load |
No Yes |
|||||
Switching frequency | ||||||
● with resistive load, max. ● with inductive load, max. ● on lamp load, max. ● of the pulse outputs, with resistive load, max. |
100 Hz 0.5 Hz 100 Hz 2.5 kHz |
|||||
Total current of the outputs (per group) | ||||||
horizontal installation | ||||||
— up to 40 °C, max. — up to 60 °C, max. |
3 A 2 A |
|||||
vertical installation | ||||||
— up to 40 °C, max. | 2 A | |||||
Cable length | ||||||
● shielded, max. ● unshielded, max. |
1 000 m 600 m |
|||||
Analog inputs | ||||||
Number of analog inputs ● For voltage/current measurement ● For resistance/resistance thermometer measurement |
5 4 1 5; 4x current/voltage, 1x resistance 5 V; Permanent 30 V; Permanent 0.5 mA; Permanent 50 mA; Permanent 400 Hz 3.3 V 1.25 mA Yes; Degrees Celsius / degrees Fahrenheit / Kelvin |
|||||
integrated channels (AI) | ||||||
permissible input voltage for current input (destruction limit), max. | ||||||
permissible input voltage for voltage input (destruction limit), max. | ||||||
permissible input current for voltage input (destruction limit), max. | ||||||
permissible input current for current input (destruction limit), max. | ||||||
Electrical input frequency, max. | ||||||
No-load voltage for resistance-type transmitter, typ. | ||||||
Constant measurement current for resistance-type transmitter, typ. | ||||||
Technical unit for temperature measurement adjustable | ||||||
Input ranges | ||||||
● Voltage ● Current ● Resistance thermometer ● Resistance |
Yes; ±10 V / 100 kΩ; 0 V to 10 V / 100 kΩ Yes; ±20 mA / 100 Ω; 0 mA to 20 mA / 100 Ω; 4 mA to 20 mA / 100 Ω Yes; Pt 100 / 10 MΩ Yes; 0 Ω to 600 Ω / 10 MΩ |
|||||
Input ranges (rated values), voltages | ||||||
● 0 to +10 V — Input resistance (0 to 10 V) |
Yes 100 kΩ |
|||||
Input ranges (rated values), currents | ||||||
● 0 to 20 mA — Input resistance (0 to 20 mA) ● -20 mA to +20 mA — Input resistance (-20 mA to +20 mA) ● 4 mA to 20 mA — Input resistance (4 mA to 20 mA) |
Yes 100 Ω Yes 100 Ω Yes 100 Ω |
|||||
Input ranges (rated values), resistance thermometer | ||||||
● Pt 100 | Yes | |||||
— Input resistance (Pt 100) | 10 MΩ | |||||
Input ranges (rated values), resistors | ||||||
● 0 to 600 ohms — Input resistance (0 to 600 ohms) |
Yes 10 MΩ | |||||
Thermocouple (TC) | ||||||
Temperature compensation | ||||||
— parameterizable | No | |||||
Characteristic linearization | ||||||
● parameterizable — for resistance thermometer |
Yes; by software Pt 100 |
|||||
Cable length | ||||||
● shielded, max. | 100 m | |||||
Analog outputs | ||||||
Number of analog outputs | 2 2 Yes 55 mA 14 V |
|||||
integrated channels (AO) | ||||||
Voltage output, short-circuit protection | ||||||
Voltage output, short-circuit current, max. | ||||||
Current output, no-load voltage, max. | ||||||
Output ranges, voltage | ||||||
● 0 to 10 V ● -10 V to +10 V |
Yes Yes |
|||||
Output ranges, current | ||||||
● 0 to 20 mA ● -20 mA to +20 mA ● 4 mA to 20 mA |
Yes YesYes |
|||||
Connection of actuators | ||||||
● for voltage output two-wire connection ● for voltage output four-wire connection ● for current output two-wire connection |
Yes; Without compensation of the line resistances No Yes |
|||||
Load impedance (in rated range of output) | ||||||
● with voltage outputs, min. ● with voltage outputs, capacitive load, max. ● with current outputs, max. ● with current outputs, inductive load, max. |
1 kΩ 0.1 µF 300 Ω 0.1 mH |
|||||
Destruction limits against externally applied voltages and currents | ||||||
● Voltages at the outputs towards MANA ● Current, max. |
16 V; Permanent 50 mA; Permanent |
|||||
Cable length | ||||||
● shielded, max. | 200 m | |||||
Analog value generation for the inputs | ||||||
Measurement principle | Actual value encryption (successive approximation) | |||||
Integration and conversion time/resolution per channel | ||||||
● Resolution with overrange (bit including sign), max. ● Integration time, parameterizable ● Interference voltage suppression for interference frequency f1 in Hz ● Time constant of the input filter ● Basic execution time of the module (all channels released) |
12 bit Yes; 16.6 / 20 ms 50 / 60 Hz 0.38 ms 1 ms |
|||||
Analog value generation for the outputs | ||||||
Integration and conversion time/resolution per channel | ||||||
● Resolution with overrange (bit including sign), max. ● Conversion time (per channel) |
12 bit 1 ms |
|||||
Settling time | ||||||
● for resistive load ● for capacitive load ● for inductive load |
0.6 ms 1 ms 0.5 ms |
|||||
Encoder | ||||||
Connection of signal encoders | ||||||
● for voltage measurement ● for current measurement as 2-wire transducer |
Yes Yes; with external supply |
|||||
● for current measurement as 4-wire transducer ● for resistance measurement with two-wire connection ● for resistance measurement with three-wire connection ● for resistance measurement with four-wire connection |
Yes Yes; Without compensation of the line resistances No No |
|||||
Connectable encoders | ||||||
● 2-wire sensor — permissible quiescent current (2-wire sensor), max. |
Yes 1.5 mA |
|||||
Errors/accuracies | ||||||
Temperature error (relative to input range), (+/-) | 0.006 %/K 60 dB 0.06 % 0.1 % 0.15 % 0.01 %/K 60 dB 0.06 % |
|||||
Crosstalk between the inputs, min. | ||||||
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | ||||||
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | ||||||
Linearity error (relative to output range), (+/-) | ||||||
Temperature error (relative to output range), (+/-) | ||||||
Crosstalk between the outputs, min. | ||||||
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | ||||||
Operational error limit in overall temperature range | ||||||
● Voltage, relative to input range, (+/-) ● Current, relative to input range, (+/-) ● Resistance, relative to input range, (+/-) ● Voltage, relative to output range, (+/-) ● Current, relative to output range, (+/-) |
1 % 1 % 1 % 1 % 1 % |
|||||
Basic error limit (operational limit at 25 °C) | ||||||
● Voltage, relative to input range, (+/-) ● Current, relative to input range, (+/-) ● Resistance, relative to input range, (+/-) ● Resistance thermometer, relative to input range, (+/-) ● Voltage, relative to output range, (+/-) ● Current, relative to output range, (+/-) |
0.8 %; Linearity error ±0.06 % 0.8 %; Linearity error ±0.06 % 0.8 %; Linearity error ±0.2 % 0.8 % 0.8 % 0.8 % |
|||||
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | ||||||
● Series mode interference (peak value of interference < rated value of input range), min. ● Common mode interference, min. |
30 dB 40 dB |
|||||
Interfaces | ||||||
Number of industrial Ethernet interfaces | 0 0 2; MPI and PROFIBUS DP 0 |
|||||
Number of PROFINET interfaces | ||||||
Number of RS 485 interfaces | ||||||
Number of RS 422 interfaces | ||||||
1. Interface | ||||||
Interface type | Integrated RS 485 interface No |
|||||
Isolated | ||||||
Interface types | ||||||
● RS 485 ● Output current of the interface, max. |
Yes 200 mA |
|||||
Protocols | ||||||
● MPI ● PROFIBUS DP master ● PROFIBUS DP slave ● Point-to-point connection |
Yes
No No No |
|||||
MPI | ||||||
● Transmission rate, max. | 187.5 kbit/s | |||||
Services | ||||||
— PG/OP communication — Routing — Global data communication — S7 basic communication — S7 communication — S7 communication, as client — S7 communication, as server |
Yes Yes Yes Yes Yes; Only server, configured on one side No; but via CP and loadable FB Yes |
|||||
2. Interface | ||||||
Interface type | Integrated RS 485 interface Yes |
|||||
Isolated | ||||||
Interface types | ||||||
● RS 485 ● Output current of the interface, max. |
Yes 200 mA | |||||
Protocols | ||||||
● MPI ● PROFINET IO Controller ● PROFINET IO Device ● PROFINET CBA ● PROFIBUS DP master ● PROFIBUS DP slave ● Point-to-point connection |
No
No No No Yes Yes No |
|||||
PROFIBUS DP master | ||||||
● Transmission rate, max. ● Number of DP slaves, max. |
12 Mbit/s 124 |
|||||
Services | ||||||
— PG/OP communication — Routing — Global data communication — S7 basic communication — S7 communication — S7 communication, as client — S7 communication, as server — Equidistance — Isochronous mode — SYNC/FREEZE — Activation/deactivation of DP slaves — Number of DP slaves that can be simultaneously activated/deactivated, max. — Direct data exchange (slave-to-slave communication) — DPV1 |
Yes
Yes No Yes No Yes Yes 8 |
|||||
Address area | ||||||
— Inputs, max. — Outputs, max. |
2 kbyte 2 kbyte |
|||||
User data per DP slave | ||||||
— Inputs, max. — Outputs, max. |
244 byte 244 byte |
|||||
PROFIBUS DP slave | ||||||
● GSD file ● Transmission rate, max. ● automatic baud rate search ● Address area, max. ● User data per address area, max. |
The latest GSD file is available on the Internet (http://www.siemens.com/profibus-gsd) 12 Mbit/s Yes; only with passive interface 32 32 byte |
|||||
Services | ||||||
— PG/OP communication — Routing — Global data communication — S7 basic communication — S7 communication — S7 communication, as client — S7 communication, as server — Direct data exchange (slave-to-slave communication) — DPV1 |
Yes Yes; Only with active interface No No Yes; Only server, configured on one side No Yes Yes No |
|||||
Transfer memory | ||||||
— Inputs — Outputs |
244 byte 244 byte |
|||||
Protocols | ||||||
PROFIsafe | No | |||||
communication functions / header | ||||||
PG/OP communication | Yes Yes |
|||||
Data record routing | ||||||
Global data communication | ||||||
● supported | Yes | |||||
● Number of GD loops, max. | 8 | |||||
● Number of GD packets, max. | 8 | |||||
● Number of GD packets, transmitter, max. | 8 | |||||
● Number of GD packets, receiver, max. | 8 | |||||
● Size of GD packets, max. | 22 byte | |||||
● Size of GD packet (of which consistent), max. | 22 byte | |||||
S7 basic communication | ||||||
● supported | Yes | |||||
● User data per job, max. | 76 byte | |||||
● User data per job (of which consistent), max. | 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) | |||||
S7 communication | ||||||
● supported | Yes | |||||
● as server | Yes | |||||
● as client | Yes; Via CP and loadable FB | |||||
● User data per job, max. | 180 kbyte; With PUT/GET | |||||
● User data per job (of which consistent), max. | 240 byte; as server | |||||
S5 compatible communication | ||||||
● supported | Yes; via CP and loadable FC | |||||
Number of connections | ||||||
● overall | 12 | |||||
● usable for PG communication | 11 | |||||
— reserved for PG communication | 1 | |||||
— adjustable for PG communication, min. | 1 | |||||
— adjustable for PG communication, max. | 11 | |||||
● usable for OP communication | 11 | |||||
— reserved for OP communication | 1 | |||||
— adjustable for OP communication, min. | 1 | |||||
— adjustable for OP communication, max. | 11 | |||||
● usable for S7 basic communication | 8 | |||||
— reserved for S7 basic communication | 0 | |||||
— adjustable for S7 basic communication, min. | 0 | |||||
— adjustable for S7 basic communication, max. | 8 | |||||
● usable for routing | 4; max. | |||||
S7 message functions | ||||||
Number of login stations for message functions, max. | 12; Depending on the configured connections for PG/OP and S7 basic | |||||
communication | ||||||
Process diagnostic messages | Yes | |||||
simultaneously active Alarm-S blocks, max. | 300 | |||||
Test commissioning functions | ||||||
Status block | Yes; Up to 2 simultaneously Yes 4 |
|||||
Single step | ||||||
Number of breakpoints | ||||||
Status/control | ||||||
● Status/control variable | Yes | |||||
● Variables | Inputs, outputs, memory bits, DB, times, counters | |||||
● Number of variables, max. | 30 | |||||
— of which status variables, max. | 30 | |||||
— of which control variables, max. | 14 | |||||
Forcing | ||||||
● Forcing ● Forcing, variables ● Number of variables, max. |
Yes Inputs, outputs 10 |
|||||
Diagnostic buffer | ||||||
● present | Yes | |||||
● Number of entries, max. — adjustable — of which powerfail-proof ● Number of entries readable in RUN, max. — adjustable — preset |
500 No 100; Only the last 100 entries are retained 499 Yes; From 10 to 499 10 |
|||||
Service data | ||||||
● can be read out | Yes | |||||
Interrupts/diagnostics/status information | ||||||
Diagnostics indication LED | ||||||
● Status indicator digital input (green) ● Status indicator digital output (green) |
Yes Yes | |||||
Integrated Functions | ||||||
Counter ● Number of counters ● Counting frequency, max. |
4; See “Technological Functions” manual 60 kHz Yes 4; up to 60 kHz (see “Technological Functions” manual) Yes Yes; PID controller (see “Technological Functions” manual) Yes 4; Pulse width modulation up to 2.5 kHz (see “Technological Functions” Manual) 2.5 kHz |
|||||
Frequency measurement ● Number of frequency meters |
||||||
controlled positioning | ||||||
integrated function blocks (closed-loop control) | ||||||
PID controller | ||||||
Number of pulse outputs | ||||||
Limit frequency (pulse) | ||||||
Potential separation | ||||||
Potential separation digital inputs | ||||||
● Potential separation digital inputs ● between the channels ● between the channels and backplane bus |
Yes
No Yes |
|||||
Potential separation digital outputs | ||||||
● Potential separation digital outputs ● between the channels ● between the channels, in groups of ● between the channels and backplane bus |
Yes
Yes 8 |
|||||
Potential separation analog inputs | ||||||
● Potential separation analog inputs ● between the channels ● between the channels and backplane bus |
Yes; common for analog I/O No Yes |
|||||
Potential separation analog outputs | ||||||
● Potential separation analog outputs ● between the channels ● between the channels and backplane bus |
Yes; common for analog I/O No Yes |
|||||
Isolation | ||||||
Isolation tested with | 600 V DC | |||||
Ambient conditions | ||||||
Ambient temperature during operation | ||||||
● min. ● max. |
0 °C 60 °C |
|||||
configuration / header | ||||||
Configuration software | ||||||
● STEP 7 ● STEP 7 Lite |
Yes; STEP 7 V5.5 + SP1 or higher or STEP 7 V5.3 + SP2 or higher with HSP 203 No |
|||||
configuration / programming / header | ||||||
● Command set ● Nesting levels ● System functions (SFC) ● System function blocks (SFB) |
see instruction list 8 see instruction list see instruction list |
|||||
Programming language | ||||||
— LAD — FBD |
Yes Yes |
|||||
— STL — SCL — CFC — GRAPH — HiGraph® |
Yes
Yes Yes Yes |
|||||
Know-how protection | ||||||
● User program protection/password protection ● Block encryption |
Yes Yes; With S7 block Privacy |
|||||
Dimensions | ||||||
Width | 120 mm 125 mm 130 mm |
|||||
Height | ||||||
Depth | ||||||
Weights | ||||||
Weight, approx. | 680 g |
Reviews