CPU processing times | |
for bit operations, typ. | 150 ns; / instruction 1.2 µs; / instruction 3.6 µs; / instruction |
for word operations, typ. | |
for floating point arithmetic, typ. | |
Address area | |
I/O address area | |
● Inputs ● Outputs |
144 byte; 256 bit of digital inputs & 56 words of analog inputs
144 byte; 256 bit of digital outputs & 56 words of analog outputs |
Time of day | |
Clock | |
● Type ● Hardware clock (real-time) ● Backup time ● Deviation per day, max. |
Hardware clock, no battery backup Yes 7 d 120 s; within 120s/month at 25 °C |
Digital inputs | |
Number of digital inputs ● of which inputs usable for technological functions |
18 6; HSC (High Speed Counting) Yes |
Source/sink input | |
Number of simultaneously controllable inputs | |
all mounting positions | |
— up to 40 °C, max. | 18 |
Input voltage | |
● Type of input voltage | DC |
● Rated value (DC) | 24 V |
● for signal “0” | 5 V DC at 1 mA |
● for signal “1” | 15 V DC at 2.5 mA |
Input current | |
● for signal “0”, max. (permissible quiescent current) ● for signal “1”, typ. |
1 mA 4 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
— parameterizable | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in |
groups of four | |
— at “0” to “1”, min. | 0.2 ms |
— at “0” to “1”, max. | 12.8 ms |
for interrupt inputs | |
— parameterizable | Yes |
for technological functions | |
— parameterizable | Yes; 6 Single phase: 5 HSCs at 200 kHz; 1 HSCs at 30 kHz 4 A/B phase: 3 HSCs at 100 kHz; 1 HSC at 20 kHz |
Cable length | |
● shielded, max. ● unshielded, max. |
500 m; 50m shielded for HSC inputs 300 m; for technological functions: No |
Digital outputs | |
Number of digital outputs | 12; Relays |
Switching capacity of the outputs | |
● with resistive load, max. ● on lamp load, max. |
2 A 30 W; 30 W with DC, 200 W with AC |
Output delay with resistive load | |
● “0” to “1”, max. ● “1” to “0”, max. |
10 ms; max. 10 ms; max. |
Switching frequency | |
● of the pulse outputs, with resistive load, max. | 1 Hz |
Relay outputs | |
● Number of relay outputs | 12 |
Cable length | |
● shielded, max. ● unshielded, max. |
500 m 150 m |
Interfaces | |
Number of industrial Ethernet interfaces | 1 |
Number of RS 485 interfaces | 1 |
1. Interface | |
Interface type | PROFINET |
Isolated | Yes; Transformer isolated, 1,500V AC |
automatic detection of transmission rate | Yes; 10/100 Mbit/s |
Autonegotiation | Yes |
Autocrossing | Yes |
Interface types | |
● RJ 45 (Ethernet) | Yes |
Protocols | |
● PROFINET IO Controller ● PROFINET IO Device |
Yes; Since V2.4 Yes; I-Device since V2.5 |
PROFINET IO Controller | |
● Transmission rate, max. | 100 Mbit/s |
Services | |
— Number of connectable IO Devices, max. — Updating time |
8 4 ms; The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. |
Address area | |
— Inputs, max. — Outputs, max. |
128 byte; Per device 128 byte; Per device |
2. Interface | |
Interface type | RS 485 (max. 187.5 kbps) |
Interface types | |
● RS 485 | Yes |
PROFIBUS DP master | |
Services | |
— S7 communication | Yes |
Protocols | |
Supports protocol for PROFINET IO | Yes; RT Controller (since FW V2.4) & I-Device (since FW V2.5) Yes; Via CM DP module |
PROFIBUS | |
Protocols (Ethernet) | |
● TCP/IP | Yes |
communication functions / header | |
S7 communication | |
● supported ● as server ● as client |
Yes
Yes Yes |
Test commissioning functions | |
Forcing | |
● Forcing | Yes |
Integrated Functions | |
Counter ● Number of counters |
6 Yes; PID closed-loop control function: Continuous controller outputs, binary controller outputs, automatic/manual mode, max. 8 loops 3 |
PID controller | |
Number of pulse outputs | |
EMC | |
Interference immunity against discharge of static electricity | |
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 — Test voltage at air discharge — Test voltage at contact discharge |
Yes 8 kV 4 kV |
Interference immunity against high-frequency electromagnetic fields | |
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-3 | Yes; 10 V/m, 80 to 1 000 MHz (to IEC 61000-4-3); 10 V/m, 900 MHz, 1.89 GHz, 50% ED (to IEC 61000-4-3) |
Interference immunity to cable-borne interference | |
● Interference immunity on supply lines acc. to IEC 61000- 4-4 ● Interference immunity on signal cables acc. to IEC 61000- 4-4 |
Yes; 2 kV acc. to IEC 61000-4-4, burst Yes; ±2 kV acc. to IEC 61000-4-4, Burst |
Interference immunity against conducted variable disturbance induced by high-frequency fields | |
● Interference immunity against high frequency current feed acc. to IEC 61000-4-6 | Yes; 10 V, 150 kHz to 80 MHz (to IEC 61000-4-6) |
Emission of radio interference acc. to EN 55 011 | |
● Limit class A, for use in industrial areas | Yes; EN 61000-6-4, interference emission: Intended for use in industrial areas. |
Emission of conducted and non-conducted interference | |
● Interference emission via line/AC current cables | EN 61000-6-4, interference emission: Intended for use in industrial areas. |
Degree and class of protection | |
IP degree of protection | IP20 |
Standards, approvals, certificates | |
CE mark | Yes |
Ambient conditions | |
Free fall | |
● Fall height, max. | 0.3 m; five times, in product package |
Ambient temperature during operation | |
● min. ● max. ● horizontal installation, min. ● horizontal installation, max. ● vertical installation, min. ● vertical installation, max. |
0 °C 55 °C 0 °C 55 °C 0 °C 45 °C |
Ambient temperature during storage/transportation | |
● min. ● max. |
-40 °C 70 °C |
Air pressure acc. to IEC 60068-2-13 | |
● Storage/transport, min. ● Storage/transport, max. |
660 hPa 1 080 hPa |
Altitude during operation relating to sea level | |
● Installation altitude, min. ● Installation altitude, max. |
-1 000 m 2 000 m |
Relative humidity | |
● Operation at 25 ℃ without condensation, max. | 95 % |
configuration / header | |
configuration / programming / header | |
Programming language | |
— LAD — FBD — STL |
Yes YesYes |
Dimensions | |
Width | 110 mm 100 mm 81 mm |
Height | |
Depth |
SIMENS-6ES7288-1SR30-0AA0
** spare part *** SIMATIC S7-200 SMART, CPU SR20, CPU, AC/DC/relay,
onboard I/O: 12 DI 24 V DC; 8 DO relay 2A; power supply: AC 85-264 V AC at 47-
63 Hz, program/data memory 20 KB
Category: Automation & Instrumentation
Description
Additional information
Dimensions | 110 × 100 × 81 cm |
---|---|
Product type designation |
CPU SR30 AC/DC/Relay |
Programming package |
STEP 7 Micro/WIN SMART |
Rail mounting |
Yes; Standard – DIN rail |
Rated value (AC) ● 120 V AC |
YES |
● 230 V AC |
YES |
permissible range, | |
permissible range |
264 V |
Current consumption |
72 mA; at 240 V AC |
Current consumption, max |
136 mA; At 120 V AC |
Inrush current, max. |
8.9 A; at 264 V |
Current output, max |
300 mA; 24 V DC Sensor Power |
Power loss, max |
14 W; max |
Type of memory |
DDR |
Flash |
YES |
RAM |
YES |
Memory available |
12 kbyte |
Memory size |
18 kbyte; Program memory |
Micro Memory Card |
Yes; microSDHC Card (optional) |
Backup / present |
Yes; Maintenance free, RTC requires 7 days. |
Brand |
SIEMENS |
Reviews (0)